Is the directions right???
(At the UPS)
9 PIN D-SUB ??? at the UPS.
Pin | Description |
---|---|
1 | Unused |
2 | Battery power |
3 | Unused |
4 | Common (same as 7) |
5 | Low battery |
6 | RS-232 level shutdown |
7 | Common (same as 4) |
8 | Ground level shutdown (A500 and above, reserved on <A500) |
9 | Reserved |
Pins 2 and 5 are connected to Common when they are true.
On pin 6, an rs-232 high level (>9V) will shutdown, when
running off the battery.
On pin 8, shorting to ground will shutdown.