Документ взят из кэша поисковой машины. Адрес оригинального документа : http://www.naic.edu/~phil/hardware/generator/networkdoc/Sales%20Sheets/PCC3200NCM_S-1433.pdf
Дата изменения: Wed Feb 6 02:15:20 2013
Дата индексирования: Sun Mar 2 06:10:02 2014
Кодировка:

Поисковые слова: comet hale-bopp
PowerCommandБ Network
Communications Module for PCC 3200 Controls
(FT-10)

Description
The PCC 3200 Network Communications Module (NCM) provides an interface for a PowerCommand Genset to the PowerCommand Network. The NCM is easily installed inside the generator control box without additional wiring, conduit, or external enclosures. The NCM allows local or remote monitoring and control of the PowerCommand GenSet. The NCM allows a user to start, stop, and emergency stop, or reset a fault of the genset. The NCM may be configured for automatic alarm dial-out of genset fault conditions.

Features
· Provides simple real-time access to all necessary PowerCommand PCC 3200 genset data. · Automatic indication of genset warning and shutdown conditions to a user-defined location. · May be connected at any point in the PowerCommand Network · Module firmware can be upgraded in the field. · May be remotely monitored and controlled with ® PowerCommand Software for W indows v 2.01 · Plugs easily into genset control requiring no additional wiring, conduit or external enclosures. · Less wiring makes installation and system upgrades quick and easy

Specifications
Network
®

Echelon LonW orks , Twisted-pair 78 KBPS, FT-10

®

Temperature
Operating Storage -25 to +70 °C (-13 to +158 °F) -25 to +80 °C (-13 to +176 °F) 25 - 90% (non-condensing)

Protocol
Echelon LonW orks, GOAL

Power
Provided by PowerCommand Generator Control

Humidity
Relative

Ц

2002 Cummins Power Generation

Specifications May Change Without Notice

S-1433 (1/03)


Monitoring Information Available
Generator Voltage (3-Phase) Current (3-Phase) Percent Current Percent Load Power Factor Frequency Real Power Energy Ground Fault High/Low AC Voltage Reverse kW Reverse kVAR Overload Engine Engine Speed Engine Temperature (L & R) Exhaust Temperature (L & R) Oil Pressure Oil Temperature Low/High Battery Voltage Run Time Pre-Low Oil Pressure Pre-High Engine Temperature Overspeed Low Coolant Level Low Fuel Level AC Charger Failure Status Switch Position GenSet Status Number of Starts Model Rating Fault Status Load Demand Setting Load Ramp Setting Load Tracking

Annunciation Available*
NFPA 110 High Battery Voltage Low Battery Voltage Genset Running Pre-Low Oil Pressure Low Oil Pressure Pre-High Engine Temp High Engine Temp Low Engine Temp Overspeed Fail to Start Not in Automatic Low Fuel Low Coolant Level AC Alarms Customer Fault 2 Customer Fault 4 High AC Voltage Low AC Voltage Under Frequency Overcurrent Short Circuit Reverse Power Loss of Field Loss of AC Input Fail to Synchronize Fail to Close Overload Emergency Stop Communications Failure Common Alarm Paralleling Emergency Stop Pre-Low Oil Pressure Low Oil Pressure Pre-High Engine Temp High Engine Temp Low Engine Temp Overspeed Fail to Start Not in Automatic Low Coolant Level Fail to Synchronize Fail to Close Reverse Power Loss of Field Overload Under Frequency

* Variations are not available.

Ordering Information
Part Number 0541-0809 Description PCC 3200 Network Communications Module (NCM), FT-10 (KP60-2)

See your distributor for more information

Cummins Power Generation 1400 73rd Avenue N.E. Minneapolis, MN 55432 763.574.5000 Fax: 763.574.5298
www.cumminspower.com Cummins Power Generation is a subsidiary of Cummins Inc. PowerCommand is a registered trademark of Cummins Inc. Echelon and LONW ORKS are registered trademarks of Echelon. W indows is a registered trademark of Microsoft.

For Professional Use Only. Must be installed by a qualified service technician. Improper installation presents hazards of electrical shock and improper operation, resulting in severe personal injury and/or property damage. Back feed to a utility system can cause electrocution and/or property damage. Do not connect generator sets to any building electrical system except through an approved device or after building main switch is open.

Ц

2002 Cummins Power Generation

Specifications May Change Without Notice

S-1433 (1/03)