Документ взят из кэша поисковой машины. Адрес оригинального документа : http://www.naic.edu/~phil/hardware/generator/networkdoc/Sales%20Sheets/CCM_S-1422.pdf
Дата изменения: Wed Feb 6 02:15:14 2013
Дата индексирования: Sun Mar 2 06:05:34 2014
Кодировка:

Поисковые слова: п п п п п п п п п п п п п п п п п р п р п
PowerCommandБ Network Controls and Communications Module
(FT-10)

Description
The PowerCommand Controls and Communications Module (CCM) provides local or remote monitoring and control of power system equipment such as generator sets, transfer switches and related switchgear. The CCM includes 3-phase voltage and current inputs, 32 discrete and 10 analog inputs for comprehensive monitoring. Eight output relays allow additional control of the monitored equipment. The CCM is available for Generator Set and Transfer Switch applications as well as other applications. The CCM may be configured for automatic alarm dial-out of fault conditions.

Features
· Complete 3-phase AC monitoring including Voltage, Current, Frequency, Power Factor, Real Power, Reactive Power and Energy. · 32 discrete dry contact inputs for monitoring equipment. · 10 analog inputs for monitoring Engine Oil and Exhaust Temperatures, Oil Pressure and Genset Battery Voltage. · 8 relay outputs (Form C) for controlling equipment. · Automatic alarm dial-out of all fault conditions to a user-defined location. · Module firmware can be upgraded in the field. · Supports wide variety of temperature and pressure sensors. · May be connected at any point in the PowerCommand Network. · Output relays may be used to control genset, transfer switch, or other equipment functions. · May be remotely monitored and controlled with PowerCommand Software for W indowsр V2.0. · Potted assembly is environmentally protected. · Pluggable connectors allow one-time wiring. · Transfer Switch applications include rechargeable battery and charger.

Ц

2003 Cummins Power Generation

Specifications May Change Without Notice

S-1422a (3/03)


Specifications
Network ® Echelon L
ONW ORKS
®

,Twisted-Pair 78KBPS, FT-10

Power Voltage Current Temperature Operating Storage Humidity Relative

5 - 36 VDC, 120 VAC 1.25 A (max) -25 to +70 °C (-13 to +158 °F) -25 to +85 °C (-13 to +185 °F) 25 - 95% (non-condensing)

Protocol Echelon LonW orks, GOAL

Inputs
3-Phase Voltage 3-Phase Current 32 Discrete 10 Analog 0 - 600 VAC (Line-to-Line) 0 - 5 A (AC) Dry Contact (N.O. or N.C.) (4) 0-9 VDC, (4) 0-5 VDC, (2) 0-36 VDC Outputs (Revision B) 8 - Form C Relays 500 mA @ 125 VAC, or 2A @ 30 VDC Outputs (Beginning Revision C) 8 - Form C Relays 5 A @ 250 VAC or 3A @ 30 VDC

Generator Set Applications
AC Data
Voltage (3-Phase) Current (3-Phase) Power Factor Frequenc y Real Power Reactive Power

Engine Data
Engine Temperature Exhaust Temperature Oil Temperature Oil Pressure Genset Battery Voltage Spare Temperature Fuel Remote 3 Analog I/O Spares

Genset Status
Common Alarm Low Fuel Low Engine Temp Overspeed High Engine Temp Low Oil Pressure Pre-High Engine Temp Pre-Low Oil Pressure Genset Running Switch in Off 16 Customer Inputs

Genset Control
Start/Stop Emergency Stop Reset Fault Relay 4 Relay 5 Relay 6 Relay 7 Relay 8

Transfer Switch Applications
AC Data (Load)
Voltage (3-Phase) Current (3-Phase) Power Factor Frequenc y Real Power Reactive Power

Analog Data
CCM Battery Voltage 9 Analog I/O Spares

ATS Status
Normal Available Emergency Available Normal Connected Emergency Connected Test/Exercise Backup Source Available Low Battery Voltage* High Battery Voltage* Battery Charger Failure Bypass to Normal Bypass to Emergency Transfer Pending 16 Customer Inputs

ATS Control
Load Shed/Restore Transfer Inhibit/Enable Remote Test Retransfer Inhibit Relay 5 Relay 6 Relay 7 Relay 8

* Genset Battery Voltage.

Ц

2003 Cummins Power Generation

Specifications May Change Without Notice

S-1422a (3/03)


Dimensions Generator Set Applications

5.0 (127) 0.56 (14.2)

1.0 (25.4)

1.25 (31.7)

1.25 (31.7)

1.0 (25.4)

1.0 (25.4)

0.312 (7.9)

8.0 (203.2)

0.5 (12.7)

.75 (19)

12.0 (304.8) 12.75 (323.8) DIMENSIONS SHOWN IN INCHES (mm)

.38 (9.6)

Transfer Switch Applications

1 1/4 KO 3/4 KO

1/2 KO

4.25 (22.9)

6.0 (152.4) .38 (9.6) 12.0 (304.8) 1.0 (25.4) 6.0 (152.4)

0.312 (7.9)

.75 (19)

14.0 (355.6)

DIMENSIONS SHOWN IN INCHES (mm)

Ц

2003 Cummins Power Generation

Specifications May Change Without Notice

S-1422a (3/03)


Transfer Switch Applications
The CCM (Transfer Switch) is powered by an integral rechargeable battery (with battery charger). The battery charger requires 120 VAC. If 120 VAC is not available, order the appropriate Power Transformer Kit from the table below.

Part Number
0300-4870-01 0300-4870-02 0300-4870-03

Description (Primary Voltage)
Power Transformer Kit (208, 240, 480 VAC) Power Transformer Kit (347, 380, 416 VAC) Power Transformer Kit (600 VAC)

The following Transfer Switch options are required for complete monitoring and control of an Onan Transfer Switch.

Signal
Normal Available Emergency Available Normal Connected Emergency Connected Test/Exercise Backup Source Available High Genset Battery Low Genset Battery Load Shed* Transfer Inhibit* Remote Test*
* Transfer Switch Inputs.

Required Option
Signal Module Signal Module Normal Position Emergency Pos Signal Module Signal Module Battery Charger Battery Charger Load Shed Power Sentry Power Sentry Relay ition Relay Alarms Alarms

Ordering Information*
Model
0541-0810 0541-0811

Description
Controls Communications Module, Genset (CCM-G), FT-10 Controls Communications Module, Transfer Switch (CCM-T), FT-10

If line-to-line voltages exceed 600 VAC, external Potential Transformers (PTs) are required. A Current Transformer (CT) Kit may also be required to monitor line currents. See PowerCommand and Network Installation and Operation Manual (0900-0529).

See your distributor for more information

Cummins Power Generation 1400 73rd Avenue N.E. Minneapolis, MN 55432 763.574.5000 Fax: 763.574.5298 www.cumminspowergeneration.com

Warning: For professional use only. Must be installed by a qualified service technician. Improper installation presents hazards of electrical shock and improper operation, resulting in severe personal injury and/or property damage.

Windows is a registered trademark of Microsoft. Echelon and LONWORKS are registered trademarks of Echelon. PowerCommand is a registered trademark of Cummins Inc. Cummins Power Generation is a subsidiary of Cummins Inc. Warning: Backfeed to a utility system can cause electrocution and/or property damage. Do not connect generator sets to any building electrical system except through an approved device or after building main switch is open.

Ц

2003 Cummins Power Generation

Specifications May Change Without Notice

S-1422a (3/03)