TABLE 9. MODLON REGISTER MAPPING INFORMATION ­ FT-10 NETWORK (TEMPLATE 1) SINGLE POWERCOMMAND GENSET (CCM-G) (SHEET 1 OF 2)
ModBus Registers Structure nvoGenStatus Data Point Name [0,1] Name [2,3] Name [4,5] Name [6,7] Name [8,9] Name [10,11] Name [12,13] Name [14,15] Device Type Control Switch State1 Fault Code* Fault Type2 Percent kW Total kW NFPA 1103 Extended4 nvoGenACData Frequency Total pf Total kva Total kW Total kvar Volts ab Volts bc Volts ca Volts a Volts b Volts c Amps a Amps b Amps c Percent Amps a Percent Amps b Percent Amps c GEN[0] 40001 40002 40003 40004 40005 40006 40007 40008 40009 40010 40011 40012 40013 40014 40015 40016 40017 40018 40019 40020 40021 40022 40023 40024 40025 40026 40027 40028 40029 40030 40031 40032 40033 40034 GEN[1] 40101 40102 40103 40104 40105 40106 40107 40108 40109 40110 40111 40112 40113 40114 40115 40116 40117 40118 40119 40120 40121 40122 40123 40124 40125 40126 40127 40128 40129 40130 40131 40132 40133 40134 GEN[2] 40201 40202 40203 40204 40205 40206 40207 40208 40209 40210 40211 40212 40213 40214 40215 40216 40217 40218 40219 40220 40221 40222 40223 40224 40225 40226 40227 40228 40229 40230 40231 40232 40233 40234 GEN[3] 40301 40302 40303 40304 40305 40306 40307 40308 40309 40310 40311 40312 40313 40314 40315 40316 40317 40318 40319 40320 40321 40322 40323 40324 40325 40326 40327 40328 40329 40330 40331 40332 40333 40334 GEN[4] 40401 40402 40403 40404 40405 40406 40407 40408 40409 40410 40411 40412 40413 40414 40415 40416 40417 40418 40419 40420 40421 40422 40423 40424 40425 40426 40427 40428 40429 40430 40431 40432 40433 40434 0.1 0.00005 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.5 0.5 0.5 Hz PF KVA KW KVAR Volts Volts Volts Volts Volts Volts Amps Amps Amps % % % 0.5 % Scaling Multiplier Offset Units

* Fault codes are listed in the genset Operator 's/Service Manuals.

Data = Multiplier x (Register + Offset)

C673b Page 20 of 48


TABLE 9. MODLON REGISTER MAPPING INFORMATION ­ FT-10 NETWORK (TEMPLATE 1) SINGLE POWERCOMMAND GENSET (CCM-G) (SHEET 2 OF 2)
ModBus Registers Structure nvoGenEngData g Data Point Battery Voltage Oil Pressure Oil Temp (see Note 2) Coolant Temp Misc Temp 1 (see Note 4) Misc Temp 2 (see Note 4) Fuel Rate (see Note 3) Engine RPM Engine Starts Eng Runtime (High) (see Notes 1 and 5) Eng Runtime (Low) Total kwh (High) (see Note 1) Total kwh (Low) Total Fuel (High) (see Notes 1 and 3) Total Fuel (Low) Genset Control Start/Stop Reset GEN[0] 40035 40036 40037 40038 40039 40040 40041 40042 40043 40044 40045 40046 40047 40048 40049 40050 40051 GEN[1] 40135 40136 40137 40138 40139 40140 40141 40142 40143 40144 40145 40146 40147 40148 40149 40150 40151 GEN[2] 40235 40236 40237 40238 40239 40240 40241 40242 40243 40244 40245 40246 40247 40248 40249 40250 40251 GEN[3] 40335 40336 40337 40338 40339 40340 40341 40342 40343 40344 40345 40346 40347 40348 40349 40350 40351 GEN[4] 40435 40436 40437 40438 40439 40440 40441 40442 40443 40444 40445 40446 40447 40448 40449 40450 40451 Data = Multiplier x (Register + Offset) 0.01 Gal 1.0 kwh 0.1 Sec Scaling Multiplier Offset 0.1 0.1 0.1 0.1 0.1 0.1 0.01 1.0 1.0 Units Volts DC KPA Deg Kelvin Deg Kelvin Deg Kelvin Deg Kelvin GPH RPM starts

* Fault codes are listed in the genset Operator 's/Service Manuals.

NOTES: 1. For the Data Points Engine Runtime, the Total kwh and Total Fuel for the two registers designated as high and low are put together as an unsigned double integer. This is accomplished by multiplying the value in the high register by 65536 and adding it to the value in the low register. Most software packages automatically perform this calculation if the value is simply identified as an unsigned double integer. 2. Value not supported in the 3200 controller. 3. Value not supported in the 3100 controller. 4. Value not supported. 5. With 3100 and 2100 controllers, the units are hours. With the 3200 controller, the units are seconds. The multiplier is always 0.1 For all 3100 controllers, the values given are based on using EEPROM firmware, version 2.0 or greater. The values for Engine Runtime and Total kwh are not available on QST-30 gensets.

C673b Page 21 of 48


1

State Description Stopped Start Pending Warmup at Idle Running Cooldown at Rated Cooldown at Idle Digital Value 0 1 2 3 4

2

Fault Type Description Normal Warning Derate Shutdown with Cooldown Shutdown

Digital Value 0 1 2 3 4 5

3

NFPA110 Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 (LSB) (MSB)

4

Extended Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 (LSB) (MSB)

Description

Description

Normal Power Genset Supplying Load Genset Running Not in Auto High Battery Voltage Low Battery Voltage Charger AC Failure Fail to Start Low Coolant Temperature Pre-High Engine Temperature High Engine Temperature Pre-Low Oil Pressure Low Oil Pressure Overspeed Low Coolant Level Low Fuel Level

Check Genset Ground Fault High AC Voltage Low AC Voltage Under Frequency Overload Overcurrent Short Circuit Reverse KW Reverse KVAR Fail to Sync Fail to Close Load Demand Genset Circuit Breaker Tripped Utility Circuit Breaker Tripped Emergency Stop

C673b Page 22 of 48