Документ взят из кэша поисковой машины. Адрес оригинального документа : http://www.naic.edu/~phil/hardware/vertex/jonhagen/dc_torque.pdf
Дата изменения: Mon Feb 4 19:27:21 2008
Дата индексирования: Sat Sep 6 09:02:42 2008
Кодировка:

Поисковые слова: запрещенные спектральные линии
To: File From: Jon Hagen Date: July 5, 2002 Subject: Calculating static torque of a Kollmorgen motor from the dc currents in the three phases Summary: The torque constant for the B606A "brushless dc" motor is specified as kT = 1.651 ft lbs/ RMS Amp. When the motor is rotating at a constant speed, the current on each of the three input wires is a sine wave. These three sine wave currents have equal magnitudes and the same frequency (proportional to the motor speed), but have relative phases of 0, 2/3, and 4/3. If the RMS value of the current (which can be measured in any one of the wires if the motor is turning) is 10 amps, the motor is supplying a torque of 10 kT = 16.51 ft lbs. When the shaft is held motionless, the torque is again given by T= kT IRMS, but, in this case, the equivalent dc RMS current is calculated as IRMS = [(I12 + I22 + I32)/3]1/2 . Discussion: Suppose the shaft is held motionless. The currents in each wire will be dc (zero frequency ac) and the three current values will be different. The amplifier, using the resolver data, makes the three values proportional to cos, cos(+2/3) and cos(+4/3), where is the shaft angle (or an integral multiple of the shaft angle). Let the three currents be written as

I1 = Ipk cos , I2 = Ipk, cos (+2/3), and I3 = Ipkcos (+4/3).

1a,b,c)

The permanent magnet rotor makes the torque contributions from the three currents proportional to cos , cos(+2/3) and cos(+4/3), so the total torque is given by T = (I1 cos + I2 cos (+2/3) + I3 cos (+4/3)) or T = Ipk { (cos )2 + (cos(+2/3)) 2 + (cos(+4/3))2 }= 1.5 Ipk 2)

where is a constant proportional to kT. Note that the term in the curly brackets is identically equal to 1.5 for any value of ; this type of motor has no torque ripple as the shaft turns. From the definition of kT, and the fact that RMS current is just peak current divided by , we have T = 1.5 Ipk = kT IRMS = kT Ipk / so must be given by = kT /(1.5 ) 4) 3)


and T = kT Ipk / 5)

Let us form the root of the sum of the average squares of I1, I2, and I3. This RMS value is IRMS = [( I12 + I22 + I32 )/3]1/2 . 6)

Substituting from Equations 1a,b, and c, we find IRMS = 1.5 Ipk / or Ipk = I
RMS

/1.5

7)

Substituting Equation 7 into Equation 5, we have T = kT Ipk / = kT IRMS /(1.5 ) = kT IRMS 8)

which is the desired result. As an experimental check, a B606A motor was attached to the torque wrench and the drive was increased to produce an indicated torque of 20 ft lbs. The magnitudes of the three currents were measured using the clip-on Hall effect ammeter as 2.1A, 13.8A, and -15.7A. Using value from the motor's specification sheet, kT = 1.651 ft lbs/A we have

ft lbs

which agrees well with the indicated 20 ft lbs. The algebraic sum of the measured currents is

which indicates a slight measurement error, since this sum should be identically zero. Notes from 6-24-02 More testing in digital lab. 6V control voltage produced 40 ft lbs and a torque monitor voltage of 4.24V When cranked to saturation, the system went up to 55 ft lbs and a monitor voltage of 6.6 V. It then folded back to 40 ft lbs, again with a monitor voltage of 4.24V.

Torque/control voltage is 40/6 = 6.67 ft lbs/control volt


How much torque is needed per motor? Wt of Gregorian = 160,000 lbs 160,000/8 sin za x Rp = T in ftlbs x transmission ratio (transmision ratio = 190.07) where Rp is radius of pinion (half the pitch diamter) (1/2 (.2667m) = 5.25"=.4375') So T in ftlbs = 160,000/8 x sin za x .4375 / 190.07 = 46.03 x sin za ft lbs. T at 20 deg = 46.03 x sin(20 deg) = 15.74 ft lbs/motor Sum of Torques at 20 deg = 8 x av torque/motor = 126 ft lbs The I monitor port gives an approximation to the desired rms of the current. Probably it gives max | Ii| of the three phases. This varies between 1.4 and 1.6 of the true value 1.5, i.e. up to 6.7%too high and 6.7% too low. The Kollmorgen BD4 Amplifier Manual says: Pin 18 I monitor Torque/monitor voltage = 40/4.24 = 9.43 ftlb/monitor volt or 55/6.6 = 8.33 ftlb / monitor volts (average is 8.88 ft lb / monitor volt). Compare with specs from instruction manual: Manual says 8 monitor volts for peak current (40 amps) or 5 amps per monitor volt which would be 8 volts for 40 x 1.651 = 66 ftlbs. or 66/8 = 8.255 ft lb per monitor volt.

Non-linear relation between Torque and Monitor voltage. The Kollmorgen manual states "There is a direct relationship between the signal appearing at this output and actual motor current. A dc voltmenter placed between pin 18 and common can be used to estimate the constant load levels placed on the motor. The current scale factor is 8V = Reak RMS current rating of the BDS4 (3k Ohm oput impedance). This output is for reference only. Its accuracy decreases as current decreases: - 4% at peak current +/- 9 % at continuous current, +/- 12 % at 1/2 continous current. " (Moreover, the voltage on pin 18 is always positive - it doesn't indicate the sign of the torque. Couldn't they have done better than this?!).


Setting the Amplifier Scale Gain
The amplifier (dome amplifiers) scale factor is to be adjusted for 6.67 ft lbs/control volt. Adjust the scale pot as follows: Align the motor shaft key with the base of the pointer in the torque tester. Set the control voltage to -5.5Volts. Adjust the scale pot until the Isense voltage reading is 4.0 Volts. The torque should be 36.7 ft. lbs for this control voltage. (The pot may well be at its fully clockwise position). Maximum continuous torque, +/-33.4 ft lbs corresponds to a control voltage of +/- 5V. Maximum current (2 seconds before fold back) corresponds to a control voltage of +/10V (full scale).

Interpreting the Torque Monitor Voltage
Lab test data, Vcontrol vs. Vmonitor, suggest the following relation: |Torque in ft. lbs| = 13.3(Vmonitor).73 for Vmonitor <4 |Torque in ft. lbs| = 6.47 + 7.6 Vmonitor for Vmonitor <4 This is derived from the data shown below, where the solid line is 2(Vmonitor).73 for Vmonitor >4 and .97 +1.14 Vmonitor for Vmonitor>4. These data were taken using the torque wrench set-up at various shaft angles.

If a little error is acceptable at the top of the scale, the curve can be represented entirely by |Torque in ft. lbs| = 13.3(Vmonitor).73 for Vmonitor <4, as shown below.