Документ взят из кэша поисковой машины. Адрес оригинального документа : http://www.naic.edu/~phil/hardware/generator/generator.html
Дата изменения: Wed Dec 2 01:06:31 2015
Дата индексирования: Mon Apr 11 11:59:29 2016
Кодировка:
generators (cummings)  

Cummings diesel generators

20Nov13

01dec13: generator startup with site as load.
19nov13:Monitoring generators with sband Tx on
    -Performance
Usage:
Documentation:

Intro

    The site has 4 1 MegaWatt  Cummings generators. They are used for backup site power and running the sband transmitter.

Monitoring the generators. 

  The generators can be queried using the modbus protocol. The program that does this:



01dec13: Generator startup with site as load.

    The power failed on Sunday 01dec13 at 17:39:20. The site was the generator load.
The plots show the generators for  the first 10 minutes after startup (.ps) (.pdf):

Summary:

processing: x101/131202/genstartup.pro

19Nov13: first look at data while sband transmitter is on.

    Data was taken on 19Nov13 while the sband transmitter was in operation. They sband  was transmitting around 850 KWatts.

    The plots show the generator performance for 3 hours (.ps) (.pdf)

Summary:

Performance for  the 3 generators combined:

Power
2180 KW
Full power
11 KW
startup (cooling off)
80 KW
startup (cooling on)

Pumps use 70 KW
powerFactor
> .9
above 750 KW
fuel consumption
linear  above 700 KW

26 Gal/Hour
startup cooling off. Fuel rate for no load.
31 Gal/Hour
startup cooling on
187 Gal/Hour
full power
Efficiency
KW for 1 Gal/Hour
Efficiency
1 Gallon of diesel = 40.7 KWHr
11.8 KW
29%
Full Power
2.5
6%
pumps on, no HV xmter
.7 KW
1.7%
pumps off, no load.
processing:x101/131119/cgen.pro


Usage (top)

    Hour used and fuel consumed .. by generator and totals.

processing: x101/generator/chkusage.pro


Documentation:  (top)



<- page up

home_~phil